Характеристики
E5CC-T/E5AC-T/E5EC-T
|
E5CC-T
|
E5EC-T
|
E5AC-T
|
Sizes in mm (W × H × D)
|
48×48×60
|
48×96×60
|
96×96×60
|
Supply voltage
|
100 to 240 VAC 50/60Hz or 24 VAC/VDC
|
Sensor input
|
Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
|
Control mode
|
2-PID control (with auto-tuning) or ON/OFF control
|
Accuracy
|
Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. /Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.Analog input: ±0.2% FS ±1 digit max.CT input: ±5% FS ±1 digit max.Potentiometer input: ±5% FS ±1 digit max.
|
Functions
|
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tuning, PV input shift, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, moving average of input value, and display brightness setting
|
Programs / segments
|
8/32
|
PID sets
|
8
|
Communication
|
RS-485 (multi-drop), CompowayF or Modbus RTU
|
Event inputs
|
2-6
|
QLP (Quick link port)
|
Yes, via USB and E58-CIFQ2 conversion cable
|
Ambient temperature
|
-10 to 55 °C
|
IP rating of front panel
|
IP66
|
Sampling period time
|
50 ms
|
Program control
Number of programs (patterns)
|
8
|
Number of segments (steps)
|
32
|
Segment setting method
|
Time setting (Segment set with set point and time.)
|
Slope setting (Segment set with segment type, set point, slope, and time.)
|
Segment times
|
0 h 0 min to 99 h 59 min
|
0 min 0 s to 99 min 59 s
|
Alarm setting
|
Set separately for each program.
|
Reset operation
|
Select either stopping control or fixed SP operation.
|
Startup operation
|
Select continuing, resetting, manual operation, or run mode.
|
PID sets
|
Number of sets
|
8
|
Setting method
|
Set separately for each program (automatic PID group selection also supported).
|
Alarm SP function
|
Select from ramp SP and target SP.
|
Program status control
|
Segment operation
|
Advance, segment jump, hold, and wait
|
Program operation
|
Program repetitions and program links
|
Wait operation
|
Wait method
|
Waiting at segment ends
|
Wait width setting
|
Same wait width setting for all programs
|
Time signals
|
Number of outputs
|
2
|
Number of ON/OFF Operations
|
1 each per output
|
Setting method
|
Set separately for each program.
|
Program status output
|
Program end output (pulse width can be set), run output, stage output
|
Program startup operation
|
PV start
|
Select from segment 1 set point, slope-priority PV start
|
Standby
|
0 h 0 min to 99 h 59 min
|
0 day 0 h to 99 day 23h
|
Operation end operation
|
Select from resetting, continuing control at final set point, and fixed SP control.
|
Program SP shift
|
Same program SP shift for all programs
|
E5CC-T/E5AC-T/E5EC-T series optional tools
USB PC based configuration cable
|
E58-CIFQ2 for E5CC-T
|
E58-CIFQ2 (& E58-CIFQ2-E) for E5AC-T and E5EC-T
|
E5CC-T/E5AC-T/E5EC-T series software
CX-Thermo >4.62
|
Professional parameterization and cloning software, data-logging, Fine-Tuning, logic operations, easy setting of process steps
Operation system: Microsoft Windows XP (Service Pack 3 or higher)/Vista/7/8
|
Информация для заказа
E5CC-T (48 × 48 mm)
Control Output
|
Option no
|
Option description
|
Alarm outputs
|
Order code
|
100 to 240 VAC
|
24 VAC/DC
|
Out1: Relay
Out2: non
|
000
|
No option
|
3
|
E5CC-TRX3A5M-000
|
E5CC-TRX3D5M-000
|
001
|
HB/HS alarm for 1-phase heaters, 2 EV inputs
|
3
|
E5CC-TRX3A5M-001
|
E5CC-TRX3D5M-001
|
003
|
HB/HS alarm for 3-phase heaters, RS485
|
3
|
E5CC-TRX3A5M-003
|
E5CC-TRX3D5M-003
|
006
|
2 EV inputs, transfer output
|
3
|
E5CC-TRX3A5M-006
|
E5CC-TRX3D5M-006
|
Out1: Voltage (pulse)
Out2: non
|
000
|
No option
|
3
|
E5CC-TQX3A5M-000
|
E5CC-TQX3D5M-000
|
001
|
HB/HS alarm for 1-phase heaters, 2 EV inputs
|
3
|
E5CC-TQX3A5M-001
|
E5CC-TQX3D5M-001
|
003
|
HB/HS alarm for 3-phase heaters, RS485
|
3
|
E5CC-TQX3A5M-003
|
E5CC-TQX3D5M-003
|
006
|
2 EV inputs, transfer output
|
3
|
E5CC-TQX3A5M-006
|
E5CC-TQX3D5M-006
|
Out1: Linear current
Out2: non
|
000
|
No option
|
3
|
E5CC-TCX3A5M-000
|
E5CC-TCX3D5M-000
|
004
|
RS485,2 EV inputs
|
3
|
E5CC-TCX3A5M-004
|
E5CC-TCX3D5M-004
|
006
|
2 EV inputs, transfer output
|
3
|
E5CC-TCX3A5M-006
|
E5CC-TCX3D5M-006
|
Note: Other models with 2 control outputs, 4 EV inputs or with different kind of option combination are available on request. Please contact the local sales office for special request.
E5EC-T (48 × 96 mm)/E5AC-T (96 × 96 mm)
Control Output
|
Option no
|
Option description
|
Alarm outputs
|
Order code
|
100 to 240 VAC
|
24 VAC/DC
|
Out1: Relay
Out2: non
|
000
|
No option
|
4
|
E5_C-TRX4A5M-000
|
E5_C-TRX4D5M-000
|
008
|
HB/HS alarm for 1-phase heaters, RS485, 2 EV inputs
|
4
|
E5_C-TRX4A5M-008
|
E5_C-TRX4D5M-008
|
019
|
HB/HS alarm for 1-phase heaters, 6 EV inputs, transfer output
|
4
|
E5_C-TRX4A5M-019
|
E5_C-TRX4D5M-019
|
Out1: Voltage (pulse)
Out2: non
|
000
|
No option
|
4
|
E5_C-TQX4A5M-000
|
E5_C-TQX4D5M-000
|
008
|
HB/HS alarm for 1-phase heaters, RS485, 2 EV inputs
|
4
|
E5_C-TQX4A5M-008
|
E5_C-TQX4D5M-008
|
019
|
HB/HS alarm for 1-phase heaters, 6 EV inputs, transfer output
|
4
|
E5_C-TQX4A5M-019
|
E5_C-TQX4D5M-019
|
Out1: Linear current
Out2: non
|
000
|
No option
|
4
|
E5_C-TCX4A5M-000
|
E5_C-TCX4D5M-000
|
004
|
RS485, 2 EV inputs
|
4
|
E5_C-TCX4A5M-004
|
E5_C-TCX4D5M-004
|
021
|
6 EV inputs, transfer output
|
4
|
E5_C-TCX4A5M-021
|
E5_C-TCX4D5M-021
|
022
|
RS485, 4 EV inputs, transfer output
|
4
|
E5_C-TCX4A5M-022
|
E5_C-TCX4D5M-022
|
Out1: Relay
Out2: Relay
Positional proportional control model
|
000
|
No option
|
4
|
E5_C-TPR4A5M-000
|
E5_C-TPR4D5M-000
|
004
|
RS485, 2 EV inputs
|
4
|
E5_C-TPR4A5M-004
|
E5_C-TPR4D5M-004
|
022
|
RS485, 4 EV inputs, transfer output
|
4
|
E5_C-TPR4A5M-022
|
E5_C-TPR4D5M-022
|
Note: Other models with 2 control outputs or with different kind of option combination are available on request. Please contact the local sales office for special request. Replace “_” with “A” for E5AC or “E” for E5EC